Home » Shop » hot sale » Absolute Process Instruments APD 1420 D _ RTD input dual alarm

Absolute Process Instruments APD 1420 D _ RTD input dual alarm

Original price was: $319.20.Current price is: $181.06.

Sale!

51 in stock

SKU: APD 1420 D Category:

Absolute Process Instruments APD 1420 D _ RTD input dual alarm

Cecomp Electronics, APD 1420 D, Dual Alarm Trip for RTD Input, 9-30 VDC, 10-32 VAC Power

Features with all optional accessories:

  • 2-wire or 3-wire RTD
  • Lead wire compensation for 3-wire
  • User adjustable setpoint(s)
  • User adjustable deadband(s)
  • 8 Amp SPDT contacts
  • Input LoopTracker LED
  • Alarm status LEDs
  • Alarm options: LO, HI/HI, LO/LO
  • Optional reverse acting
  • Optional latching alarms
  • Push to test/reset
  • Remote push to test/reset
  • Full I/O/power isolation
  • Removable plugs
  • DIN rail mount without tools

Applications:

  • Process Limit Alarm
  • Monitor, Heaters, Refrigerators, Ovens
  • Process Signal Over or Under Alarms

The APD 1420 D accept an RTD temperature input and provide a visual alarm indication and alarm relay contact outputs. The input type, range, and alarm types are factory configured. The input can be configured for most 10 Ω to 2000 Ω RTDs. Front-accessible potentiometers are used to adjust alarm setpoint and deadband.

LoopTracker and Alarm Status LEDs

API exclusive features include a LoopTracker LED that varies in intensity with changes in the process input signal. A two red/green bi-color alarm status LED visually indicate alarm status. These LEDs provide a quick visual picture of your process at all times.

Output Test / Unlatch

API’s exclusive Output Test button can be used to verify the alarm and system operation and also provides the additional function of unlatching the alarm when the latching option has been ordered. This feature can be remotely operated. The output test button greatly aids in saving time during initial startup and/or troubleshooting.

Specifications Table:

Input 10, 100 or 1000 Ohm RTD
Output Two 8 Amp DPST Relays
Power to input isolation 1200 V
Common mode protection 600 VACp or 600 VDC
Temperature Input Range Factory configured, please specify the following resistance at 0°C, curve, temperature range.

  • RTD types: 10 Ω to 2000 Ω
  • RTDs including 100 Ω 0.00385 DIN, 100 Ω 0.003916, 100 Ω 0.00392, 10 Ω Cu, 1000 Ω Ni-Fe, 120 Ω Ni
  • Temperature range: °F or °C 100°F (55°C) min. span or consult factory
Leadwire Compensation <±0.05% of span per 1 Ω change in leadwire resistance
Standard Alarm Configuration 2 setpoints, 2 SPDT relays. HI/LO alarms, non-latching, normal acting
Setpoint 12 turn potentiometer adjustable from 0 to 100% of span
Deadband 12 turn potentiometer adjustable from 1 to 100% of span
Response Time 70 milliseconds typical
Ambient Temperature Range and Stability “10°C to +60°C operating ambient
Connectors Four 4-terminal removable connectors, 14 AWG max wire size
Power 9-30 VDC or 10-32 VAC