Home » Shop » hot sale » Absolute Process Instruments APD 1600 D _ AC Input Alarm Trips, Isolated

Absolute Process Instruments APD 1600 D _ AC Input Alarm Trips, Isolated

Original price was: $311.20.Current price is: $186.66.

Sale!

42 in stock

SKU: APD 1600 D Category:

Absolute Process Instruments APD 1600 D _ AC Input Alarm Trips, Isolated

Cecomp Electronics, APD 1600 D, Single Alarm Trip, 0-50 mVAC to 0-300 VAC Factory Configured Input, 9-30 VDC, 10-32 VAC Power

Features with all optional accessories:

  • Measurements are true RMS
  • User adjustable setpoint(s)
  • User adjustable deadband(s)
  • 8 Amp SPDT contacts
  • Input LoopTracker LED
  • Alarm status LEDs
  • Alarm options: LO, HI/HI, LO/LO, band alarm
  • Optional reverse acting
  • Optional latching alarms
  • Push to test/reset
  • Remote push to test/reset
  • Full I/O/power isolation
  • Removable plugs
  • DIN rail mount without tools
  • Factory Set AC Input Range
  • Alarm Test, Optional Reset Button

Applications:

  • Process Limit Backup Alarm
  • Over or Under Voltage or Current Alarm
  • Heater Break, Conveyor Jam Alarm

The APD 1600 D accept an AC voltage or milliamp current input and provide a visual alarm indication and alarm relay contact outputs. The input type, range, and alarm types are factory configured. Front-accessible potentiometers are used to adjust alarm setpoint and deadband.

LoopTracker and Alarm Status LEDs

API exclusive features include a LoopTracker LED that varies in intensity with changes in the process input signal. A red/green bi-color alarm status LED visually indicate alarm status. These LEDs provide a quick visual picture of your process at all times.

Output Test / Unlatch

API’s exclusive Output Test button can be used to verify the alarm and system operation and also provides the additional function of unlatching the alarm when the latching option has been ordered. This feature can be remotely operated.

The output test button greatly aids in saving time during initial startup and/or troubleshooting.

Specifications Table:

Input 0-50 mVAC to 0-300 VAC, 0-1 mAAC to 0-1000 mAAC
Output Two 8 Amp SPDT Relays
Power to input isolation 1200 V
Common mode protection 750 VACp or 750 VDC
AC Input Range Factory configured, please specify input type and range. Consult factory for special ranges.

  • Voltage: 0-50 mVAC to 0-300 VAC
  • Current: 0-1 mAAC to 0-1000 mAAC
  • Measurements are true RMS
Input Impedance 220 kΩ minimum
Input Voltage Burden (Current Input) 1.0 VRMS maximum
Input Frequency 40 Hz to 1000 Hz sinusoidal
Excitation Voltage Factory configured, please specify excitation voltage, Refer to the sensor manufacturer’s recommendations.

  • Excitation: 1 to 10 VDC, 30 mA max.
  • Fine adjustment: Approximately ±0.25 VDC
  • Stability: ±0.01% per °C
  • Designed for one 350 W (or greater) sensor
Standard Alarm Configuration Single setpoint dual SPDT relays. HI alarm, non-latching, normal acting
Setpoint 12 turn potentiometer adjustable from 0 to 100% of span
Deadband 12 turn potentiometer adjustable from 1 to 100% of span
Response Time 70 milliseconds typical
Ambient Temperature Range and Stability “10°C to +60°C operating ambient
Connectors Four 4-terminal removable connectors, 14 AWG max wire size
Power 9-30 VDC or 10-32 VAC 50/60 Hz, 2 W maximum