Home » Shop » hot sale » Absolute Process Instruments APD 4380 _DC TO DC ISOLATED TRANSMITTER – FIELD CONFIGURABLE

Absolute Process Instruments APD 4380 _DC TO DC ISOLATED TRANSMITTER – FIELD CONFIGURABLE

Original price was: $343.20.Current price is: $265.78.

Sale!

11 in stock

SKU: APD 4380 Category:

Absolute Process Instruments APD 4380 _DC TO DC ISOLATED TRANSMITTER – FIELD CONFIGURABLE

Cecomp Electronics, APD 4380, DC to DC Isolated Signal Conditioner, 53 Field Configurable Input Range, 85-265 VAC, 60-300 VDC Power

Features:

  • One Minute Setup for Hundreds of I/O Ranges
  • External Switches & Tables for Range Selection
  • Zero and Span Output Calibration Potentiometers
  • Full 1200 V Input/Output/Power Isolation
  • Input and Output LoopTracker® LEDs
  • Output Test Button
  • Built-In Loop Power Supplies for Sink/Source I/O

Applications:

  • Convert, Boost, and Rescale Process Signals
  • Isolate Single-Ended (Common Ground) PLC Inputs
  • Interface Process Signals with Panel Meters, PLCs, Recorders, Data Acquisition, DCS, & SCADA Systems

The APD 4380 accepts a DC voltage or current input and provides an optically isolated DC voltage or current output that is linearly related to the input.

Typical applications include signal isolation, conversion, boosting or a combination of the three. Full 3-way isolation (input, output, power) makes this module useful for ground loop elimination, common mode signal rejection or noise pickup reduction.

I/O Sink/Source Versatility

Standard on the APD 4380 is a 15 VDC loop excitation supply for the input and a 20 VDC loop excitation supply for the output. These power supplies can be used to power passive mA devices if required.

For maximum versatility the input and output can each be selectively wired for sinking or sourcing. This allows the APD 4380 to work with any combination of powered or unpowered mA inputs and powered or unpowered mA outputs.

LoopTracker

API exclusive features include two LoopTracker LEDs (green for input, red for output) that vary in intensity with changes in the process input and output signals. These provide a quick visual picture of your process loop at all times and can greatly aid in saving time during initial startup and/or troubleshooting.

Output Test

An API exclusive feature includes the test button to provide a fixed output (independent of the input) when held depressed. The test output level is potentiometer adjustable from 0 to 100% of output span. The output test button greatly aids in saving time during initial startup and/or troubleshooting.

Specifications Table:

Input 0-10 mV to 0-130 VDC, ±5 mVDC to ±65 VDC, 0-200 µA to 0-50 mADC (Sink or Source)
Output 0-1 V to 0-10 VDC, ±5 VDC, ±10 VDC, 0-2 mA to 4-20 mA (Sink or Source)
DC Input Ranges

Field selectable ranges and offsets via switch settings

Voltage: 0-10 mVDC to 0-130 VDC

Bipolar voltage: ±5 mVDC to ±65 VDC

Current: 0-200 µADC to 0-50 mADC

Input offset: ±100% in 15% increments

Input Impedance (Voltage)

Voltage: 1 MΩ minimum

Current: 50 Ω typical

Voltage burden: 1 VDC at 20 mA current input

Common Mode Rejection 100 dB minimum
Input Loop Power Supply 15 VDC ±10%, regulated, 25 mADC. May be selectively wired for sinking or sourcing mA input
Output Loop Power Supply 20 VDC nom., regulated, 25 mADC, <10 mVRMS max. ripple. May be selectively wired for sinking or sourcing mA output
DC Output Ranges

Field selectable ranges and offsets via switch settings

Voltage (10 mA max): 0-1 VDC to 0-10 VDC

Bipolar voltage: ±5 VDC or ±10 VDC

Current: 0-2 mADC to 0-20 mADC, 4-20 mADC 20 V compliance, 1000 Ω at 20 mA

Output Loop Power Supply

20 VDC nominal, regulated, 25 mADC, <10 mVRMS max. ripple

May be selectively wired for sinking or sourcing mA output

Output Test/Override

Front button sets output to test level when pressed or via external contact closure

Potentiometer adjustable 0-100% of span

Output Ripple and Noise Less than 10 mVRMS ripple and noise
Linearity Better than ±0.1% of span
Ambient Temperature Range and Stability

-10°C to +60°C operating ambient

Better than ±0.02% of span per °C stability

Response Time

Standard: 70 milliseconds nominal

DF option: 1 millisecond nominal. Output noise levels will be greater than standard specifications. Consult factory

Isolation 1200 VRMS minimum Full isolation: power to input, power to output, input to output
Housing and Connectors
  • IP 40, requires installation in panel or enclosure
  • For use in Pollution Degree 2 Environment
  • Mount vertically to a 35 mm DIN rail
  • Four 4-terminal removable connectors, 14 AWG max wire size
Power 85-265 VAC, 50/60 Hz or 60-300 VDC, 2 W maximum