Home » Shop » hot sale » Absolute Process Instruments APD 7010 _ transmitter. Fully isolated.

Absolute Process Instruments APD 7010 _ transmitter. Fully isolated.

Original price was: $327.20.Current price is: $228.79.

Sale!

18 in stock

SKU: APD 7010 Category:

Absolute Process Instruments APD 7010 _ transmitter. Fully isolated.

Cecomp Electronics, APD 7010, Frequency to DC Isolated Signal Conditioner, 85-265 VAC, 60-300 VDC Power

Features:

  • Precision Frequency to DC Converter
  • Zero and Span Output Calibration Potentiometers
  • Full 1200 V Input / Output / Power Isolation
  • Input and Output LoopTracker® LEDs
  • Output Test Button
  • Built-In Loop Power Supply for Sink/Source Output

Applications:

  • Monitor and Control Motor or Line Speed
  • Convert Speed and Frequency Signals
  • Simplify Interfacing of Frequency Sensors

The APD 7010 accepts a frequency input and provides an optically isolated DC voltage or current analog output that is linearly proportional to the input.

The full 3-way (input, output, power) isolation between input and output makes this module useful for ground loop elimination, common mode signal rejection, and noise pickup reduction.

Also standard on the APD 7010 is a 15 VDC input excitation supply. If needed, this supply can be used to power a passive sensor, eliminating the need for an additional external power supply.

Common applications include frequency to DC conversions from frequency output type devices such as rotary encoders, magnetic pick-ups, variable speed drives and flow meters.

A PLC pulse rate output can be programmed to vary. By connecting the APD 7010 to this output, a proportional analog signal can be generated.

Sink / Source Versatility

For maximum versatility the output can be selectively wired for sinking (unpowered) or sourcing (powered) milliamp output. The 20 VDC loop excitation supply can be used to power a milliamp current loop if required. The output can also be wired for an externally powered loop.

LoopTracker

API exclusive features include two LoopTracker LEDs (green for input, red for output) that vary in intensity with changes in the process input and output signals. These provide a quick visual picture of your process loop at all times and can greatly aid in saving time during initial startup and/or troubleshooting.

Output Test

An API exclusive feature includes the test button to provide a fixed output (independent of the input) when held depressed. The test output level is potentiometer adjustable 100% of the output span. The output test button greatly aids in saving time during initial startup and/or troubleshooting.

Specifications Table:

Input Factory ranged 0-25 Hz to 0-20 kHz
Output 0-1 V to 0-10 VDC, ±1 VDC to ±10 VDC, 0-1 mA to 20 mADC (Factory ranged voltage or milliamps)
Frequency Input Range Factory configured, please specify input range

  • Frequency: 0-25 Hz to 0-20 kHz
  • Sine wave, sawtooth, or square wave with min. 5 µsec pulse
Input Amplitude Range 100 mV to 150 VRMS (Any waveform with minimum 100 mV amplitude change)
Input Impedance
  • 10 kW nominal (maximum sensitivity)
  • 100 kW nominal (minimum sensitivity)
Input Sensitivity/Hysteresis Multi-turn potentiometer for sensitivity adjustment

  • Maximum sensitivity: ±25 mV typical
  • Minimum sensitivity: ±2.5 V typical
Input Protection
  • Normal mode: 200% of input rating
  • Common mode: 600 VDC or 600 VACp input to ground
Input Power Supply
  • 15 VDC ±10%, regulated, 25 mADC
  • Max. ripple, less than 10 mVRMS
  • May be used to power sensor
DC Output Range Factory configured, please specify output range

  • Voltage: 0-1 VDC to 0-10 VDC
  • Bipolar voltage: ±1 VDC to ±10 VDC
  • Current: 0-2 mADC to 0-20 mADC, 20 V compliance, 1000 Ω at 20 mA
Output Calibration Multi-turn zero and span potentiometers, ±15% adj. range typ.
Output Loop Power Supply
  • 20 VDC nominal, regulated, 25 mADC
  • Max. ripple, less than 10 mVRMS

May be selectively wired for sinking or sourcing mA output

Output Test/Override Front momentary button or external contact closure sets output to test level. Potentiometer adjustable 0-100% of span.
Output Ripple and Noise Less than 10 mVRMS ripple and noise
Linearity Better than ±0.1% of span
Ambient Temperature Range and Stability
  • “10°C to +60°C operating ambient
  • Better than ±0.02% of span per °C stability
Isolation
  • 1200 VRMS minimum
  • Full isolation: power to input, power to output, input to output
Housing
  • IP 40, requires installation in panel or enclosure
  • For use in Pollution Degree 2 Environment
  • Mount vertically to a 35 mm DIN rail
Connectors Four 4-terminal removable connectors, 14 AWG max wire size
Power 85-265 VAC, 50/60 Hz or 60-300 VDC, 2.5 W maximum