Absolute Process Instruments T16ADA2 _ transmitter. Fully isolated.

Cecomp Electronics, T16ADA2, ThermoPro® Temperature Alarm, 2.5″ Fixed Probe Length

Features:

  • 100 Ω Platinum RTD
  • 316 Stainless Steel Probe
  • Programmable SPDT Relays
  • -58.0°F to 392.0°F or -50.0°C to 200.0°C
  • NEMA 4X Housing
  • User-programmable setpoints
  • User configurable relay operation
  • Pass code protected setup and calibration

Specifications Table:

Range “58.0 to 392.0°F or “50.0 to 200.0°C, selectable
Resolution 0.1 degree resolution
Typical Accuracy Includes linearity error and ±1 LSD 11-point linearization

  • ±0.7°C at “50°C
  • ±0.4°C at 0°C
  • ±0.9°C at 100°C
  • ±1.4°C at 200°C
Display
  • 4 readings per second nominal display update rate
  • 4 digit LCD, 0.5″ H
  • 5 character 0.25″ H alphanumeric
  • Low battery voltage indication(ALARM1 under range indication on display, ALARM2 over range indication on display)
Sensor
  • IEC-751 Class B 100 Ω Platinum RTD, 0.00385 alpha curve 1 /2″ NPT male, 316L stainless steel
  • All wetted parts are 316L stainless steel
  • Fixed probe pressure rating: 5000 psi max.
  • Fixed probes are welded to hex fitting
Controls and Functions
  • 4 button front keypad for setup, calibration, and configuration.
  • Multi-level user-defined pass codes to prevent unauthorized changes.
  • Pass code optional for output test and set point changes.
  • Pass code required for configuration and calibration.
Output Test Function
  • Test mode to toggle alarm relays
  • Output test function can be pass code protected
Relay Output
  • Two independent SPDT relays 0.5A/115VAC, 1A/24VDC, non-inductive
  • Alarm status updated 4 times per second nominal
  • Alarm configuration mode can be pass code protected
  • Each alarm programmable for either HI or LO set point
  • Each alarm programmable for deadband in degrees
  • Selectable upscale or downscale burnout
  • Selectable normal or reverse alarm action
  • Factory defaults: °F temperature scale, SP1 HI, SP2 LO, 1° deadband, downscale burnout, normal alarm action, configuration and test mode not pass code protected.
  • 3 ft long, 6-conductor 22 AWG cable for relays
Calibration
  • User settable pass code required to enter calibration mode
  • Zero and span temperature calibration
  • Non-interactive zero, span, and linearity, ±10% of range
Power
  • 8 to 24 VAC 50/60 Hz or 9 to 32 VDC
  • Reverse polarity protected
  • 3 ft long, 2-conductor 22 AWG cable for power
Weight
  • Product: 12 ounces (approximately)
  • Shipping: 1 pound (approximately)
Housing Materials ABS/polycarbonate NEMA 4X case, rear gasket, polycarbonate label, aluminum sensor block
Storage Temperature “40 to 203°F (“40 to 95°C)
Operating Range “4 to 185°F (“20 to 85°C) at housing
Cable Length 2.5″